Commissioning 4.2.3 Paral shift Press the selector . Turn the selector and set the most suitable value. Press the selector to confirm. IMPORTANT: If the room temperature is higher than the desired value, the curve must be shifted lower. If the room temperature is too low, the curve should be shifted upwards. If the temperature of the room corresponds with the desired value, the curve is correct. In the graph below, the curves have been divided into two groups: – Low-temperature systems – High temperature systems The two groups are divided according to the different point of origin of the curves, which for high-temperature systems is higher than 10°C, a correction usually made to the delivery temperature in these types of systems during climatic adjustment. 4.2.4 Room Influence Proportional Turn the selector and set the most suitable value, then press the selector to confirm. The influence of the room sensor can be adjusted to a value between 20 (maximum influence) and 0 (no influence). In this way, the contribution of the room temperature to the delivery temperature calculation can be adjusted. 4.2.5 Max T Turn the selector press the selector 4.2.6 Min T Turn the selector press the selector then set the most suitable value and to confirm. then set the most suitable value and to confirm. 4.2.7 Thermoregulation logic Turn the selector then set the most suitable value and press the selector to confirm. Turn the selector and select: 0 Classic. 1 Smart Smart temperature control (in this mode, the water flow set-point is calculated using the information provided in parameter 4.7 Zone regulation parameters) 4.2.8 Quick night setback Turn the selector then set the most suitable value and press the selector to confirm. Turn the selector and select: 0 OFF. 1 ON. 4.2.9 Heat request mode Turn the selector then set the most suitable value and press the selector to confirm. Turn the selector and select: 0 Standard. 1 RT Time Programs Exclusion (In this mode, the heat requests generated by the RT remain active also during the night-time period in programmed mode). 2 Forcing Heat Demand (The activation of this function generates a constantly active heat request). Repeat the steps described previously to set the values for zone 2 (where present), by selecting the 5 Zone 2 parameters menu. NOTE: For correct operation of the temperature adjustment types: 2. Room sensor only: 3. Outdoor sensor only: 4. Room sensor plus external sensor, parameter 1.0.6 Thermoregulation should be set to value 1, or the AUTO function must be activated. 4.3 DIAGNOSTICS 4.3.0 Room T 4.3.1 Room T setpoint 4.3.2 Flow temperature 4.3.3 Return temperature 4.3.4 Heat Request Z1 Press the selector . Turn the selector to choose the desired item. 0 OFF. 1 ON. Press the selector to confirm. 4.3.5 Pump status Press the selector . Turn the selector to choose the desired item. 0 OFF. 1 ON. Press the selector to confirm. 4.3.7 Relative humidity 4.3.8 Zone flow temperature setpoint 58 / EN
Commissioning 4.4 ZONE MODULE SETTINGS 4.4.0 Zone pump modulation Press the selector . Turn the selector to choose the desired item. 0 Fixed. 1 Modulating on DeltaT. 2 Modulating on pressure. Press the selector to confirm. 4.4.1 Target deltaT for pump modulation 4.4.2 Pump fixed speed 4.5 COOLING 4.5.0 T Set Cool Press the selector . Turn the selector and set the delivery setpoint temperature value, if temperature control is deactivated or with fixed point. Fan coil units °C 1 15 14 13 12 18 23 28 33 11 10 9 8 7 6 8 14 19 24 29 34 39 44 °C 2 4.5.1 Cooling Temp Range Press the OK button. Turn the selector and select the temperature range: 0 Fan Coil. 1 Underfloor. 1 Delivery temperature to the system 2 Outside air temperature Under-floor system Fig. 69 4.5.2 Thermoregulation Press the selector , turn the selector and set the type of temperature control installed: 0 ON/OFF Thermostat (Fixed water flow set-point specified in Par. 4.5.0 T Set Cool). 1 Fix Flow T (Fixed water flow set-point specified in Par. 4.5.0 T Set Cool). 2 Outdoor T Only (Water flow set-point according to the outdoor temperature). 4.5.3 Slope Press the selector . Turn the selector and set the curve on the basis of the type of cooling system. Press the selector to confirm. – Fan coil units (curve from 18 to 33). – Underfloor heating system (curve from 0 to 60). The checking process for the suitability of the curve requires a long period of time during which several adjustments may be necessary. °C 1 23 22 21 20 19 18 17 16 15 30 25 20 15 10 5 0 14 8 14 19 24 29 34 39 44 °C 2 Fig. 70 1 Delivery temperature to the system 2 Outside air temperature When the outdoor temperature rises (summer), three conditions may arise: – The room temperature increases, indicating that a gentler curve must be set. – The room temperature decreases, indicating that a steeper curve must be set. – The temperature of the room remains constant, indicating that the set curve is exactly right. Once you have found the curve which maintains the room temperature at a constant level, check the actual temperature value. 59 / EN
NIMBUS HYBRID MODULE UNIVERSAL 3301
Contents 1. Safety advices 1.1
a a a a a a a When connecting the c
Loading...
Loading...
Commissioning 4.2.3 Paral shift Press the selector . Turn the selector and set the most suitable value. Press the selector to confirm. IMPORTANT: If the room temperature is higher than the desired value, the curve must be shifted lower. If the room temperature is too low, the curve should be shifted upwards. If the temperature of the room corresponds with the desired value, the curve is correct. In the graph below, the curves have been divided into two groups: – Low-temperature systems – High temperature systems The two groups are divided according to the different point of origin of the curves, which for high-temperature systems is higher than 10°C, a correction usually made to the delivery temperature in these types of systems during climatic adjustment. 4.2.4 Room Influence Proportional Turn the selector and set the most suitable value, then press the selector to confirm. The influence of the room sensor can be adjusted to a value between 20 (maximum influence) and 0 (no influence). In this way, the contribution of the room temperature to the delivery temperature calculation can be adjusted. 4.2.5 Max T Turn the selector press the selector 4.2.6 Min T Turn the selector press the selector then set the most suitable value and to confirm. then set the most suitable value and to confirm. 4.2.7 Thermoregulation logic Turn the selector then set the most suitable value and press the selector to confirm. Turn the selector and select: 0 Classic. 1 Smart Smart temperature control (in this mode, the water flow set-point is calculated using the information provided in parameter 4.7 Zone regulation parameters) 4.2.8 Quick night setback Turn the selector then set the most suitable value and press the selector to confirm. Turn the selector and select: 0 OFF. 1 ON. 4.2.9 Heat request mode Turn the selector then set the most suitable value and press the selector to confirm. Turn the selector and select: 0 Standard. 1 RT Time Programs Exclusion (In this mode, the heat requests generated by the RT remain active also during the night-time period in programmed mode). 2 Forcing Heat Demand (The activation of this function generates a constantly active heat request). Repeat the steps described previously to set the values for zone 2 (where present), by selecting the 5 Zone 2 parameters menu. NOTE: For correct operation of the temperature adjustment types: 2. Room sensor only: 3. Outdoor sensor only: 4. Room sensor plus external sensor, parameter 1.0.6 Thermoregulation should be set to value 1, or the AUTO function must be activated. 4.3 DIAGNOSTICS 4.3.0 Room T 4.3.1 Room T setpoint 4.3.2 Flow temperature 4.3.3 Return temperature 4.3.4 Heat Request Z1 Press the selector . Turn the selector to choose the desired item. 0 OFF. 1 ON. Press the selector to confirm. 4.3.5 Pump status Press the selector . Turn the selector to choose the desired item. 0 OFF. 1 ON. Press the selector to confirm. 4.3.7 Relative humidity 4.3.8 Zone flow temperature setpoint 58 / EN
Commissioning 4.4 ZONE MODULE SETTINGS 4.4.0 Zone pump modulation Press the selector . Turn the selector to choose the desired item. 0 Fixed. 1 Modulating on DeltaT. 2 Modulating on pressure. Press the selector to confirm. 4.4.1 Target deltaT for pump modulation 4.4.2 Pump fixed speed 4.5 COOLING 4.5.0 T Set Cool Press the selector . Turn the selector and set the delivery setpoint temperature value, if temperature control is deactivated or with fixed point. Fan coil units °C 1 15 14 13 12 18 23 28 33 11 10 9 8 7 6 8 14 19 24 29 34 39 44 °C 2 4.5.1 Cooling Temp Range Press the OK button. Turn the selector and select the temperature range: 0 Fan Coil. 1 Underfloor. 1 Delivery temperature to the system 2 Outside air temperature Under-floor system Fig. 69 4.5.2 Thermoregulation Press the selector , turn the selector and set the type of temperature control installed: 0 ON/OFF Thermostat (Fixed water flow set-point specified in Par. 4.5.0 T Set Cool). 1 Fix Flow T (Fixed water flow set-point specified in Par. 4.5.0 T Set Cool). 2 Outdoor T Only (Water flow set-point according to the outdoor temperature). 4.5.3 Slope Press the selector . Turn the selector and set the curve on the basis of the type of cooling system. Press the selector to confirm. – Fan coil units (curve from 18 to 33). – Underfloor heating system (curve from 0 to 60). The checking process for the suitability of the curve requires a long period of time during which several adjustments may be necessary. °C 1 23 22 21 20 19 18 17 16 15 30 25 20 15 10 5 0 14 8 14 19 24 29 34 39 44 °C 2 Fig. 70 1 Delivery temperature to the system 2 Outside air temperature When the outdoor temperature rises (summer), three conditions may arise: – The room temperature increases, indicating that a gentler curve must be set. – The room temperature decreases, indicating that a steeper curve must be set. – The temperature of the room remains constant, indicating that the set curve is exactly right. Once you have found the curve which maintains the room temperature at a constant level, check the actual temperature value. 59 / EN
NIMBUS HYBRID MODULE UNIVERSAL 3301
Contents 1. Safety advices 1.1
a a a a a a a When connecting the c
Loading...
Loading...
X