AIR INTAKE EXHAUST AIR

AIR INTAKE EXHAUST AIR INTAKE INSTALLATION 120 180 195 105 Fig. 9 For coaxial systems, the maximum development value, mentioned in the table below also takes into account an elbow. For twin flue systems the maximum development value, mentioned in the table includes the exhaust gas/air intake terminal. AIR INTAKE MUST NOT BE FITTED ABOVE THE EXHAUST Twin flue systems outlets should respect the following instructions: 1- Use the same ø 80 mm flue pipes for the air intakes and exhaust gas ducts. 2- If you need to insert elbows in the air intake and exhaust gas ducts, you should consider for each one the equivalent length to be included in the calculation of developed length. 3- The exhaust gas duct should jut above the roof by at least 0.5 m. 4- The intake and exhaust gas ducts in Type C13 + C53 must be installed on the same wall, or where the exhaust is vertical and the air intake horizontal, the terminals must be on the same side of the building. Fig. 10 22 /

INSTALLATION Table of flue gas exhaust duct lengths FLUE TYPE Coaxial System Twin-pipe System Maximum Extension Exhaust-air (m) ALTEAS ONE NET 30 35 Diameter of pipe (mm) C13 C33 7 6 ø 60/100 C43 C13 C33 C43 20 24 ø 80/125 S1 = S2 C13 30 = 30 23 = 23 C33 40 = 40 30 = 30 ø 80/80 C43 30=30 23 = 23 C53 S1 + S2 60 45 ø 80/80 S1 = Air intake S2 = Flue gas exhaust S1 = S2 - Air intake and flue gas exhaust equal lengths S1 + S2 - Air intake and flue gas exhaust unequal lengths TYPE C13 TYPE C33 TYPE C33 TYPE C33 TYPE C53 / 23