Views
3 years ago

Alteas ONE Net - Installation Manual

  • Text
  • Boiler
  • Heating
  • Flue
  • Appliance
  • Valve
  • Efficiency
  • Installation
  • Maintenance
  • Display
  • Maximum
  • Alteas

INSTALLATION BEFORE THE

INSTALLATION BEFORE THE DEVICE IS USED, FOR THE FIRST TIME THE TRAP MUST BE FILLED WITH WATER. The siphon is filled with water during deaeration procedure of the boiler (or heating system) - see p. 32 Ensure that the siphon contains water; if not, it must be refilled. Open the manual air vent (2) on the main exchanger until complete filling. Check again the system pressure on the pressure gauge. Water circuit diagram 1 3 4 5 6 21 WARNING! INSUFFICIENT WATER IN THE TRAP CAN TEMPORARILY CAUSE THE FLUE GAS TO BE EXPELLED INTO THE SURROUNDING AMBIENT AIR 7 8 9 10 12 11 20 19 18 17 16 15 14 13 A B C D E 1. Air relief valve 3. Main Heat Exchanger 4. Detection/Ignition electrode 5. Central Heating Return Temperature Probe 6. Central Heating Flow Temperature Probe 7. Gas Valve 8. Secondary Exchanger 9. Safety valve 10. Automatic By-pass 11. Drain valve 12. Condensate Trap 13. Filling loop 14. Central Heating Filter 15. D.H.W. Flow Switch 16. Diverter valve 17. Pressure Gauge 18. Water pressure sensor 19. Modulating Circulation Pump with air release valve 20. Expansion Vessel 21. Modulating Fan 16 /

INSTALLATION Connecting the Flue Flue System The provision for satisfactory flue termination must be made as described in BS 5440-1. The appliance must be installed so that the flue terminal is exposed to outdoor air. The terminal must not discharge into another room or space such as an outhouse or lean-to. It is important that the position of the terminal allows a free passage of air across it at all times. The terminal should be located with due regard for the damage or discolouration that might occur on buildings in the vicinity, it must also be located in a place not likely to cause nuisance. In cold or humid weather water vapour may condense on leaving the flue terminal. The effect of such “steaming” must be considered. If the terminal is less than 2 metres above a balcony, above ground or above a flat roof to which people have access, then a suitable stainless steel terminal guard must be fitted. The minimum acceptable spacing from the terminal to obstructions and ventilation openings are specified in Fig. 1. Fig. 1 - A Directly below an opening, window, etc 300 mm - B Horizontally to an opening, window, etc 300 mm - C Below gutters, soils pipes or drain pipes 75 mm - D Below eaves 200 mm - E From vertical drain pipe or soil pipe 75 mm - F From internal or external corner 300 mm - G Above ground, roof or balcony level 300 mm - H From a surface facing the terminal 600 mm - I From a terminal facing a terminal 1200 mm - J Vertically from a terminal on the same wall 1500 mm - K Horizontally from an terminal on the same wall 300 mm - L Fixed by vertical flue terminal Minimum Length = 500 mm 180 mm 150 mm 118 mm Fig. 2 / 17

MANUALS